pcs.pngPORTABLE CHILLER SYSTEMS

» For process cooling requirements down to -20°F (-29°C)
» Air or water-cooled condensing up to 40 Ton capacities with scroll compressor technology
» Available in single and dual circuit, combination heating/chilling systems and modulating designs
  Read More

Iceman LT Series

Mokon's Iceman LT Series line of portable chillers are available in air-cooled and water-cooled models with up to 12 Tons nominal chilling capacities and operating temperatures from -20 to +20°F (-29 to -7°C).  They feature nonferrous components and a semi-hermetic discus compressor, providing superior energy efficiency, robust operation and easy maintenance. 

Cylinder unloading/hot gas bypass used for capacity control, increasing the longevity of the compressor, is provided along with a microprocessor-based controller for extreme accuracy. The Iceman LT chillers utilize R-507 refrigerant which provides customers with an environmentally friendly option to CFCs and HCFCs. Mokon's Low Temperature Chillers are ideal for jacketed vessels, reactors, laboratory, sanitary and other industrial applications.

   
Model Cooling
Capacity
(BTU/hr) 1
Fluid Temp
-20F (-29C)

Cooling
Capacity
(BTU/hr) 1
Fluid Temp
20F (-7C)
Pump
(Hp)
Min / Max 
Flow Rate
(GPM)
Nominal
Pressure
(PSI)
Process
Connection
(FNPT)
Tank
Size
(Gal.)
 Dimensions3
L x W x H
(Approx.)
Shipping3
Weight
(Approx. lbs.)
ALT-2 12,635 38,095 2 4 / 30 Up to 35 1-1/2" 68 80" x 40" x 65" 850
ALT-3 17,480
50,065 2 7 / 40 Up to 40 1-1/2" 68 80" x 40" x 65" 850
ALT-5 27,170
77,235 3 12 / 50 Up to 50 1-1/2" 68 80" x 40" x 65" 950
ALT-7.5 38,950
107,350 5 18 / 60 Up to 60 2" 68 80" x 52" x 65" 1,300
ALT-10 48,925
141,550 5 24 / 60 Up to 55
2" 68 80" x 52" x 65" 1,400
     
   
Model Cooling
Capacity
(BTU/hr) 2
Fluid Temp
-20F (-29C)
Cooling
Capacity
(BTU/hr) 2
Fluid Temp
20F (-7C)
Pump
(Hp)
Min / Max
Flow Rate
(GPM)
Nominal
Pressure
(PSI)
Process 
Connections
(FNPT)
Condenser 
Connections
(FNPT)
Tank
Size
(Gal.)
Dimensions3
L x W x H
(Approx.)
 Shipping3
Weight
(Approx. lbs.)
WLT-2 13,870 40,565 2 4 / 30 Up to 35 1-1/2" 1" 68 80" x 40" x 65" 850
WLT-3 19,000
52,915
2 7 / 40 Up to 40 1-1/2" 1" 68 80" x 40" x 65" 850
WLT-5 29,830
81,985
3 12 / 50 Up to 50 1-1/2" 1-1/2" 68 80" x 40" x 65" 950
WLT-7.5 42,750
114,950
5 18 / 60 Up to 60 2" 1-1/2" 68 80" x 52" x 65" 1,300
WLT-10 53,675
150,100
5 24 / 60 Up to 55
2" 1-1/2" 68 80" x 52" x 65" 1,400
   


1 Air-cooled based on -20 to +20°F chilled water at 2.4 GPM/Ton and 90°F ambient air.
2 Water-cooled based on -20 to +20°F chilled water at 3 GPM/Ton and 85°F condensing water.
3 Additional features, options or modifications may alter the dimensions, shape and weight of system.
Standard compressor is semi-hermetic discus type.
1 Ton = 12,000 BTUs per hour / 1 kW = 1000 Watt = 3,412 BTU
Capacities based on the use of 50% water/ethylene glycol mix.
Iceman LT Chillers are available in a variety of voltages, capacities, and process fluid temperatures. Please contact Mokon for more information.

Product Features

Low_Temp_Chiller_Inside_Shot_for_Web.jpg

A• Non-proprietary microprocessor-based controller mounted in operator-friendly orientation
B• NEMA rated electrical enclosure with safety door disconnect switch
C• Semi-hermetic discus compressor
D• Cylinder unloading/hot gas bypass circuit
E• Air-cooled condenser (shown) or water-cooled condenser
F• Highly efficient brazed plate evaporator
G• Insulated nonferrous plumbing and components (shown without insulation)
H• Stainless steel centrifugal supply pump
I• Heavy-duty insulated plastic tank
 
  Additional Features:
  • NFPA 79 electrical safety standards
  • UL 508A labeled electrical sub-panel
  • Easy-to-access control panel
  • Durable, powder coated cabinetry

Options

* Please consult factory for more information.
Air filters
Alarms - audible and visual
Auto fill
Control options - remote setpoint and re-transmission, communication ports, and much more
Low water level indication
Other voltages, phases, frequencies
Phase indicator
Power cord
Process purge (manual & automatic)
Pump modifications to increase flow capacity or elimination of supply pump
Remote condenser
Special paint
Tank upgrades and modifications
Thermometers
Valved process bypass
Water filters

Controls

Features of Standard and Optional Controls
A variety of controls are available from Mokon to enhance the high performance of our systems. From solid state to microprocessor based, with communication capabilities to PLC type controls, Mokon can provide the type of control package right for your process. 

 
Eurotherm 3216 Series
The Eurotherm 1/16 DIN (3216) microprocessor controller is operator friendly and easy-to-use. Standard features include a microprocessor controller for the highest accuracy in temperature control, a dual LCD display that shows set point and actual fluid temperature, and scrolling text messages that deliver plain language messages to let users know exactly what is happening to the process. There are optional 1/8 or 1/4 DIN controllers available, with high/low deviation alarm, remote set point and retransmission and serial communication. A five-year warranty comes standard with the controller.

Click on the links below for more information on the Eurotherm 3200 Series controllers:
3216 Spec Sheet 
3200 Series Manual
Control_euro3216.jpg
Custom Controls
Mokon’s ability to meet customers’ specific requirements is seen not only in custom system designs, but also in controls. Our engineers can custom design a control package that meets your specific processing needs, from brand name controls, to direct computer/host machine interfacing. All of which can be expected with the same quality and durability that our customers expect from our complete line of temperature control systems.