The Iceman Micro Series chiller is ideal for laboratory applications, laser cooling, micro molding, and other industrial applications. Constructed in a sleek space-conscious cabinet, this system can also be customized to fit into space-limiting configurations. The Micro Series chiller is available in air-cooled or water-cooled condensing both with cooling capacities of 1/4 or 1/3 Ton.
|
| Model |
Cooling
Capacity
(Tons) |
Compressor
Horsepower
(Hp) |
Pump
Horsepower
(Hp) |
Nominal
Flow Rate
(GPM) |
Nominal
Pressure
(PSI) |
Process
Connection
(FNPT) |
Process
Condenser
(FNPT) |
Tank
Size
(Gal.) |
Electrical
Service |
Dimensions
L x W x H |
Shipping
Weight
(Approx. lbs.) |
AF-1125
(Air) |
1/4 * |
1/4 |
1/8 |
0.6
(2.3 Max) |
10 |
1/2" |
N/A |
4 |
115V
Single
Phase
60 Hz |
26" x 17" x 28" |
150 |
AF-1133
(Air) |
1/3 * |
1/3 |
1/8 |
0.8
(2.3 Max) |
10 |
1/2" |
N/A |
4 |
115V
Single
Phase
60 Hz |
26" x 17" x 28" |
150 |
WF-1125
(Water) |
1/4 ** |
1/4 |
1/8 |
0.6
(2.3 Max) |
10 |
1/2" |
3/8" |
4 |
115V
Single
Phase
60 Hz |
26" x 17" x 28" |
150 |
WF-1133
(Water) |
1/3 ** |
1/3 |
1/8 |
0.8
(2.3 Max) |
10 |
1/2" |
3/8" |
4 |
115V
Single
Phase
60 Hz |
26" x 17" x 28" |
150 |
|
| |
* Based on 50°F chilled water at 2.4 gpm/Ton and 90°F ambient air
** Based on 50°F chilled water at 2.4 gpm/Ton and 60°F condensing water
Fluid temperature range is 20°F to 60°F
|
|
 |
|
 |
| Standard Features |
| • |
Insulated reservoir tank |
| • |
Efficient brazed plate evaporator |
| • |
Heavy duty insulated plastic tank |
| • |
Non-ferrous centrifugal supply pump |
| • |
Insulated non-ferrous plumbing and components |
| • |
Microprocessor-based controller mounted in operator-friendly orientation |
| • |
Pump down cycle for capacity control |
| • |
Hermetic compressors |
| • |
High and low refrigerant pressure cut-off switches |
| • |
NEMA 1 electrical enclosure |
| • |
Freeze and high return temperature protection |
|
|
|
| * Please consult factory for more information. |
 |
|
| • |
Air duct flange (top) 1/2 ton to 40 ton cabinet |
| • |
Audible alarm |
| • |
Auto fill |
| • |
Blown fuse indication |
| • |
CPR valve |
| • |
Custom controls |
| • |
Flow meters |
| • |
Low water level indication |
| • |
Low/High refrigerant gauges & thermometer (standard on 1/2 to 40 ton) |
| • |
Other voltages, phases, frequencies |
| • |
Phase indicator |
| • |
Pilot light indication (standard on 1/2 to 40 ton) |
| • |
Power cord |
| • |
Process purge (manual & automatic) |
| • |
Pump modifications to increase flow capacity or elimination of supply pump |
| • |
Remote condenser |
| • |
Special paint |
| • |
Strainers (process return) |
| • |
Tank upgrades and modifications |
| • |
TEFC motors |
| • |
Valved process bypass |
| • |
Visual alarm |
|
| |
| Features of Standard and Optional Controls |
A variety of controls are available from Mokon to enhance the high performance of our systems. From solid state to microprocessor based, with communication capabilities to PLC type controls, Mokon can provide the type of control package right for your process.
|
| Eurotherm 3216 Series |
The Eurotherm 1/16 DIN (3216) microprocessor controller is now standard on the entire line of portable chillers, water and heat transfer fluid temperature control systems. This controller is operator friendly and easy-to-use. Standard features include a microprocessor PID controller for the highest accuracy in temperature control, a dual LCD display that shows set point and actual fluid temperature, and advanced PID overshoot protection with self-tuning capabilities for increased accuracy. Scrolling text messages deliver plain language messages to let users know exactly what is happening to the process.
There are optional 1/8 or 1/4 DIN controllers available, with high/low deviation alarm, remote set point and retransmission and serial communication. A five-year warranty comes standard with the controller. |
 |
|
| Custom Controls |
| Mokon’s ability to meet customers’ specific requirements is seen not only in custom system designs, but also in controls. Our engineers can custom design a control package that meets your specific processing needs, from brand name controls, to direct computer/host machine interfacing. All of which can be expected with the same quality and durability that our customers expect from our complete line of temperature control systems. |
|
| |