Mokon's BFC Series Blown Film Air Coolers offer an increase in blown film productivity, especially in warmer climates or when ambient air temperatures rise during the summer. Mokon’s BFC Series boosts productivity by eliminating production variables in your air ring supply, including air temperature, pressure and volume.
The BFC units typically use a modulated chilled water supply to provide a constant leaving air temperature to the process. The air inlet diffuser assures that the air stream covers the full face of the cooling coil to provide optimum cooling efficiency. The leaving air chamber is insulated to reduce condensation while providing the coldest air possible to the air ring.
|
| |
| Model |
Process Air CFM |
B.t.u./Hr.of Heat Removal1 |
Nominal Cooling Required2 (Tons) |
Water Capacity (gpm) |
Chilled Water Connection (in.) |
Air Inlet/Outlet Size (in.) |
| BFC-600 |
600 |
64,512 |
5.5 |
13 |
1.0 |
10/10 |
| BFC-1000 |
1000 |
105,855 |
9 |
26 |
1.5 |
10/10 |
| BFC-1500 |
1500 |
158,861 |
13.5 |
40 |
2.0 |
14/14 |
| BFC-2000 |
2000 |
211,775 |
18 |
59 |
2.0 |
14/14 |
| BFC-3500 |
3500 |
370,470 |
31 |
81 |
2.5 |
16/16 |
| BFC-5000 |
5000 |
532,210 |
44.5 |
112 |
2.5 |
18/18 |
| BFC-7500 |
7500 |
793,760 |
66 |
126 |
3.0 |
22/22 |
| BFC-9000 |
9000 |
953,541 |
80 |
175 |
3.0 |
24/24 |
|
| |
| Model |
Dimensions Base Unit L x W x H (in.) |
Base Unit Shipping Weight (lbs.) |
Shipping Weight With 16" Blower |
Shipping Weight With 35" Blower |
Blower Motor3 16" Static Pressure (Hp) |
Blower Motor3 35" Static Pressure (Hp) |
| BFC-600 |
47 x 32 x 47 |
400 |
690 |
790 |
3 |
7.5 |
| BFC-1000 |
47 x 32 x 47 |
430 |
705 |
830 |
5 |
10 |
| BFC-1500 |
47 x 38 x 51 |
645 |
985 |
1215 |
7.5 |
15 |
| BFC-2000 |
47 x 38 x 51 |
700 |
1050 |
1325 |
10 |
20 |
| BFC-3500 |
60 x 45 x 74 |
1100 |
1580 |
2035 |
15 |
40 |
| BFC-5000 |
70 x 64 x 75 |
1600 |
2375 |
2575 |
25 |
60 |
| BFC-7500 |
70 x 73 x 84 |
1800 |
2575 |
3800 |
40 |
75 |
| BFC-9000 |
70 x 73 x 84 |
2000 |
3075 |
4300 |
40 |
75 |
|
| |
1. Based on 50°F leaving air from cooler, 80°F wet bulb ambient air temp, 40°F entering chilled water and required CFM of process air.
Please note - Heat removal value does not include heat contributed by the blower
2. Chilled water Tons required with entering air at 100°F dry bulb, 80°F wet bulb, 40°F chilled water and 50°F air leaving
3. Blower at 460 Volt, 3 Phase, 60 Hertz. (Additional voltages available, please consult factory)
|
|
 |
| |
| |
 |
|
| |
Standard Features |
| A. |
Condensate trap |
| B. |
Adjustable legs |
| C. |
Hybrid epoxy, powder coated (inside and out) cabinet |
| D. |
Zinc plated bolts spaced for 35" static pressure |
| E. |
Leaving air thermometer |
| F. |
Coil air vent |
| G. |
Chilled water inlet thermometer |
| H. |
Two-way leaving air temperature actuated valve (optional) |
| I. |
Entering air diffuser |
| J. |
Chilled water outlet thermometer and ball valve |
|
|
|
| |
| Mokon offers a variety of options and accessories to meet specific customer needs. Typical requests include custom painted colors, custom air inlet/outlet transitions, stacking ability, two- or three-way valves, 16" or 35" static pressure blowers, 5°F approach coil and other voltages. Please consult factory for more information. |
|
| |