C3 Cold Climate Cooler System offers a cost-effective solution to process cooling in cold weather areas. The system uses ambient air temperature to cool fluid in a closed loop system that requires no make-up water or expensive chemical treatments.
The C3 system saves water and energy and is environmentally friendly. The system also extends the life of your chiller. During cold weather, you can turn off your chiller and use the Cold Climate Cooler.
The C3 system is also an ideal addition to a Mokon central chiller and pump tank system. The Cold Climate Cooler can be integrated to provide maximum cooling at minimal cost!
|
| |
|
C3 Cold Climate Cooler System (Ethylene Glycol) |
| |
|
| Model |
Capacity1
(Tons) |
Flow2
(gpm) |
Fans Hp |
Fans Qty |
Dimensions
LxWxH |
Shipping
Weight (lbs) |
Voltage/Phase/Hz4 |
| FND124C-9-EG |
20 |
57 |
2 |
2 |
117" x 48" x 52" |
1,125 |
460/3/60 |
| FND134C-6-EG |
28 |
79 |
2 |
3 |
117" x 48" x 52" |
1,582 |
380/3/50 |
| FND134C-9-EG |
30 |
86 |
2 |
3 |
117" x 48" x 52" |
1,582 |
460/3/60 |
| FND224E-6-EG |
37 |
105 |
2 |
4 |
117" x 93" x 52" |
2,105 |
380/3/50 |
| FND224E-9-EG |
40 |
114 |
2 |
4 |
117" x 93" x 52" |
2,105 |
460/3/60 |
| FND154C-6-EG |
46 |
132 |
2 |
5 |
288" x 48" x 56" |
2,398 |
380/3/50 |
| FND154C-9-EG |
50 |
143 |
2 |
5 |
288" x 48" x 56" |
2,398 |
460/3/60 |
| FND154F-6-EG |
55 |
158 |
2 |
5 |
288" x 48" x 56" |
2,616 |
380/3/50 |
| FND154F-9-EG |
60 |
172 |
2 |
5 |
288" x 48" x 56" |
2,616 |
460/3/60 |
| FND243F-6-EG |
74 |
211 |
2 |
8 |
231" x 93" x 52" |
3,231 |
380/3/50 |
| FND243F-9-EG |
80 |
229 |
2 |
8 |
231" x 93" x 52" |
3,231 |
460/3/60 |
| FND254C-6-EG |
92 |
263 |
2 |
10 |
288" x 93" x 56" |
4,356 |
380/3/50 |
| FND254C-9-EG |
100 |
286 |
2 |
10 |
288" x 93" x 56" |
4,356 |
460/3/60 |
| FND254F-6-EG |
110 |
316 |
2 |
10 |
288" x 93" x 56" |
4,707 |
380/3/50 |
| FND254F-9-EG |
120 |
343 |
2 |
10 |
288" x 93" x 56" |
4,707 |
460/3/60 |
| FND264C-6-EG |
120 |
342 |
2 |
12 |
345" x 93" x 56" |
5,457 |
380/3/50 |
| FND264C-9-EG |
130 |
372 |
2 |
12 |
345" x 93" x 56" |
5,457 |
460/3/60 |
|
| |
|
C3 Cold Climate Cooler System (Propylene Glycol) |
| |
|
| Model |
Capacity1
(Tons) |
Flow3
(gpm) |
Fans Hp |
Fans Qty |
Dimensions
LxWxH |
Shipping
Weight (lbs) |
Voltage/Phase/Hz4 |
| FND124C-9-PG |
20 |
52 |
2 |
2 |
117" x 48" x 52" |
1,125 |
460/3/60 |
| FND134E-6-PG |
28 |
72 |
2 |
3 |
174" x 48" x 52" |
1,701 |
380/3/50 |
| FND134E-9-PG |
30 |
78 |
2 |
3 |
174" x 48" x 52" |
1,701 |
460/3/60 |
| FND224C-6-PG |
37 |
97 |
2 |
4 |
117" x 93" x 52" |
1,950 |
380/3/50 |
| FND224C-9-PG |
40 |
105 |
2 |
4 |
117" x 93" x 52" |
1,950 |
460/3/60 |
| FND233C-6-PG |
46 |
121 |
2 |
6 |
174" x 93" x 52" |
2,552 |
380/3/50 |
| FND233C-9-PG |
50 |
131 |
2 |
6 |
174" x 93" x 52" |
2,552 |
460/3/60 |
| FND234E-6-PG |
55 |
144 |
2 |
6 |
174" x 93" x 52" |
2,920 |
380/3/50 |
| FND234E-9-PG |
60 |
157 |
2 |
6 |
174" x 93" x 52" |
2,920 |
460/3/60 |
| FND263D-6-PG |
74 |
193 |
2 |
12 |
345" x 93" x 56" |
5,040 |
380/3/50 |
| FND263D-9-PG |
80 |
210 |
2 |
12 |
345" x 93" x 56" |
5,040 |
460/3/60 |
|
| |
|
|
| |
|
1 - Based on 1 ton of refrigeration equal to 12,000 BTUH.
2 - Flows are based on cooling 2.8 gpm per Ton of 50% water / 50% ethylene glycol.
3 - Flows are based on cooling 2.8 gpm per Ton of 60% water / 40% propylene glycol.
4 - Other voltages available include 208-240/3/60, 575/3/60 and 380/3/50.
**For higher tonnages and flow capacities, please consult the factory.**
Chiller capacities are based on cooling from 60°F to 50°F with 35°F ambient air temperature.
Specifications are for operation at elevations under 1,000 feet above sea level.
Includes motor fusing and non-fused disconnect.
Standard leg height is 22", optional heights of 36", 48" and 60" are available upon request.
|
|
|
| |